Crestron CHV-TSTAT and CHV-THSTAT Thermostats
Operations and Installation Guide DOC. 8163E Thermostats: CHV-TSTAT and CHV-THSTAT
77
Local Error Messages
When a critical sensor fails and prevents the safe or intended operation of the HVAC
equipment, an error message flashes on the main screen.
This error message appears as a text message under the line that normally reads ON
LINE and VIEW MSG. The thermostat messages are shown as follows in
descending priority.
ERROR DESCRIPTION
ERR! NO AT SRC Indicates that no air temperature source is present,
because all available sensors designated USE have
generated errors during the current read cycle. HVAC
operation is suspended and relays are cleared, except on
SLAB1 type. SLAB1 type cannot generate this error
because it does not have an air temperature USE type.
ERR! NO SB SRC Indicates that no slab temperature source is present,
because all available sensors designated SLAB have
generated errors during the current read cycle. HVAC
operation is suspended on all slab modes (1, 2, 3, 4A,
4B, 5A, 5B).
ERR! NO HM SRC Indicates that no humidity sources are present, because
all available sensors designated USE have generated
errors during the current read cycle. Humidifier operation
is suspended and HUM relay is cleared.
ERR! NO OD SRC Indicates that no outdoor source is present and the setup
says at least one remote is supposed to be providing OD
data (designated OD). This error does not disable HVAC
operation because it is not absolutely essential. All
heatpump modes that use outdoor temperature for
balance point operation eventually stage or switch to
auxiliary heat and thus prevent the space from freezing.
NOTE: All of these conditions are self-healing if the sensor begins sending valid
data.
Check Network Wiring
Use the Right Wire
In order to ensure optimum performance over the full range of the installation
topology, use Crestron Certified Wire only. Failure to do so may incur additional
charges if support is required to identify performance deficiencies because of using
improper wire.
Calculate Power
CAUTION: Use only Crestron power supplies for Crestron equipment. Failure to
do so could cause equipment damage or void the Crestron warranty.
CAUTION: Provide sufficient power to the system. Insufficient power can lead to
unpredictable results or damage to the equipment. Use the Crestron Power
Calculator to help calculate how much power is needed for the system
(www.crestron.com/calculators
).
When calculating the length of wire for a particular Cresnet run, the wire gauge and
the Cresnet power usage of each network unit to be connected must be taken into
consideration. Use Crestron Certified Wire only. If Cresnet units are to be daisy
chained on the run, the Cresnet power usage of each network unit to be daisy
Przeglądanie stron 82