Setup Mode Parameters/Functions (Continued)
PARAMETER/
FUNCTION
CODE VALID VALUES
DEFAULT
VALUE
NOTES
Perform Heat
Call Test
(Toggle)
H Not started/Heat
call off (--)
Heat call on (on)
(also, “H” icon
turns on)
N/A Tests the heat call output;
Bypasses short-cycle timers;
Useful for technician system testing;
Note that calling the heat may activate
other relays in the thermostat as required,
such as the fan output for heat pump or
dual-fuel types
Perform Cool
Call Test
(Toggle)
C Not started/Cool
call off (--)
Cool call on (on)
(also, “C” icon
turns on)
N/A Tests the cool call output. Bypasses
short-cycle timers;
Useful for technician system testing;
Note that calling the cooling may activate
other relays in the thermostat as required,
such as the fan output
Perform Fan
Call Test
(Toggle)
F Not started/Fan
call off (--)
Fan call on (on)
(also, “F” icon
turns on)
N/A Same as above, for fan;
Note that only the fan relay can be
activated for a fan call test
Perform Self
Test
St Not started (--)
In progress
(flashing --)
Finished, self test
ok (00)
Finished, self test
failed (E#, where
# represents an
error code)
N/A Refer to “Self-Test Results which starts on
page 22 for details
Verifying Communication Status
To verify communication status, enter Setup mode as described in “Basic Setup -
Basic Thermostat Setupwhich starts on page 16. Press MODE until the AC, UA or
CC function is displayed. Press
or on the CHV-TSTATEX-FCU to verify the
communication status.
Communication Error Codes
Status/
Error
Code
MEANING FOR
ACQUIREAC
MEANING FOR
UNACQUIRE “UA”
MEANING FOR
COMMUNICATION CHECK
”CC”
00 Success Success No problems found
E1 No gateway found
Failed or no previous
gateway information was
present
No gateway information present
E2
GW found but rejected
device
N/A N/A
E3
Radio operation not
available
Radio operation not
available Radio operation not available
E4 N/A N/A N/A
E5 N/A N/A N/A
E6 N/A N/A Network communication not possible
E7 N/A N/A Device not joined to a gateway
Przeglądanie stron 24
1 2 ... 20 21 22 23 24 25 26 27 28 29 30 ... 39 40

Komentarze do niniejszej Instrukcji

Brak uwag

Krystal Touch of NY DL3609CPRI manuals

Owner’s manuals and user’s guides for Unknown Krystal Touch of NY DL3609CPRI.
We providing 1 pdf manuals Krystal Touch of NY DL3609CPRI for download free by document types: Installation Guide


Table of contents





More products and manuals for Unknown Krystal Touch of NY

Models Document Type
DL3733ABPAS Installation Guide   Krystal Touch of NY DL3733ABPAS Installation Guide, 1 pages
DL3802BPRI Installation Guide   Krystal Touch of NY DL3802BPRI Installation Guide, 1 pages
DL3611CPAS Installation Guide   Krystal Touch of NY DL3611CPAS Installation Guide, 1 pages
DL3616BPAS Installation Guide   Krystal Touch of NY DL3616BPAS Installation Guide, 1 pages
DL3616CPAS Installation Guide   Krystal Touch of NY DL3616CPAS Installation Guide, 1 pages