230 V Lighting Design Guide
Doc. 4859C | crestron.com
9
CAEN Installation
The enclosure must be mounted by a licensed electrician in accordance with all national and local codes.
When choosing components to place in the enclosure, refer to the table below to ensure that the maximum weight
capacity is not exceeded. Refer to the module product page on the Crestron website for module weight.
CAUTION: These enclosures house equipment that needs to be air-cooled. Therefore, mount in a well-ventilated
area. The ambient temperature range should be 32° F to 104° F (0° C to 40° C). The relative humidity should range
from 0% to 90% (non-condensing). Furthermore, allow adequate clearance in front of the vented cover for servicing
and ventilation.
NOTES:
• Unless otherwise indicated, the lighting system specified in this guide is modular, requiring assembly in
the field by a licensed electrician, in accordance with all national and local codes. If a UL Listed panel is
required, Crestron offers this service through its UL Listed panel shop. This includes complete in factory
system configuration and assembly by Crestron for an additional fee.
• Install modules into the lowest available spaces and continue toward the top of the enclosure.
• Enclosures are intended for indoor use only.
• When flush mounting, 5/8 inch drywall is preferred.
Wiring
CAUTION: All power feeds must be protected by 15 or 20 amp circuit breakers.
NOTES:
• Use copper conductors only rated 60° C.
• All wiring must be installed in accordance with all local and national electrical codes.
• Two snap bushings are supplied. If required, insert into knockouts at the bottom of the enclosure to
prevent damage to low voltage wiring.
Class 1 and Class 2 field wires must be kept separate.
Tighten all CLT-Series terminal block screws and grounding terminal block screws to the torque specified in the
table below.
CAUTION: Failure to properly tighten the screws may result in poor electrical connection and overheating of the
terminals.
Torque Data Table
CLT Terminal Blocks Grounding Terminal Blocks
Wire Range 22-10 14-10 8 6-4
Torque (in lbs.) 9 35 40 45