Analog Input Mode
In analog input mode, the Versiport is typically tied to a resistive load (such as a
humidity sensor) or a voltage source (both can be represented by box "A" in the
Versiport diagram).
When a resistive load is tied to a Versiport, the corresponding pullup resistor must be
enabled (again, this means that <pu-disable> should be given the signal name 0 or
left undefined). This creates a voltage divider and provides a varying voltage level,
based on the current resistance of the sensor for the C2I-IO8 to read.
Example 4:
A resistive humidity sensor is tied to Versiport 1 (and <pu-disable1> is low
or undefined). <i1> will assume the corresponding analog value.
When a voltage source is tied to a Versiport, the corresponding pullup resistor should
be disabled (the only case where the default setting should be overridden). This
allows the C2I-IO8 to read the value of the voltage source directly.
Example 5:
A voltage source is tied to Versiport 1 and <pu-disable1> is given the
signal name 1. <i1> will assume the corresponding analog value (ranging
from 0 to 65535, or 0 to +10V on the input pin).
The C2I-IO8 does not propagate all changes in the analog values of its Versiports,
since this can lead to undesirable results if the input source is not clean or has jitter.
Rather, the <MinChange> signals should be used to specify a "minimum change"
value, such that the C2I-IO8 will not propagate the new value until it changes by
<MinChange>. (The default minimum change value is 2048.)
Example 6:
A voltage source is placed on Versiport 1 and <MinChange1> is set to 10
via an Analog Initialize symbol. The value of <i1> will not be propagated
until it changes by at least 10. If the current value is 500, then a new value
will not be reported until it changes to 510 or 490.
Slot 5: C2I-RY8
The C2I-RY8 provides eight isolated relays for controlling low voltage contact
closure devices such as drapes, screens and lifts.
In Program Manager, drag the C2I-RY8 symbol from Program View to Detail View.
The symbol contains the following signals:
Signals
8 relays: <A1> through <A8>
When a signal goes high, the corresponding relay closes for as long as the signal
remains high. When the signal goes low, the relay opens. If a signal is undefined, the
relay is open.
Slot 6: C2Net-Device
The C2Net-Device slot enables the PAC2 to control up to 252 Cresnet devices. Each
Cresnet device is assigned a unique identifier called a Net ID, which is a
hexadecimal value ranging from 03 to FE.
To view the list of supported devices, expand the control system in the bottom pane
of System Views and double-click the C2Net-Device slot, or right-click and select
Add Item from the submenu. Supported devices include network control modules,
lighting modules and a variety of Crestron wired touchpanels.
34 Professional Automation Computer: PAC2 Operations Guide – Doc. 5941
Przeglądanie stron 37
1 2 ... 33 34 35 36 37 38 39 40 41 42 43 ... 47 48

Komentarze do niniejszej Instrukcji

Brak uwag

Krystal Touch of NY DL3660CPRI manuals

Owner’s manuals and user’s guides for Unknown Krystal Touch of NY DL3660CPRI.
We providing 1 pdf manuals Krystal Touch of NY DL3660CPRI for download free by document types: Installation Guide


Table of contents





More products and manuals for Unknown Krystal Touch of NY

Models Document Type
DL3801BPAS Installation Guide   Krystal Touch of NY DL3801BPAS Installation Guide, 1 pages
DL3802ABPRI Installation Guide   Krystal Touch of NY DL3802ABPRI Installation Guide [no] , 1 pages
DL3612BPAS Installation Guide   Krystal Touch of NY DL3612BPAS Installation Guide, 1 pages
DL3798ABPRI Installation Guide   Krystal Touch of NY DL3798ABPRI Installation Guide, 1 pages
DL3612ABPAS Installation Guide   Krystal Touch of NY DL3612ABPAS Installation Guide, 1 pages
DL3611ABPRI Installation Guide   Krystal Touch of NY DL3611ABPRI Installation Guide, 1 pages
DL3611CPRI Installation Guide   Krystal Touch of NY DL3611CPRI Installation Guide, 1 pages
DL3612CPAS Installation Guide   Krystal Touch of NY DL3612CPAS Installation Guide, 1 pages
DL3660CPA Installation Guide   Krystal Touch of NY DL3660CPA Installation Guide, 1 pages
DL3615ABPAS Installation Guide   Krystal Touch of NY DL3615ABPAS Installation Guide, 1 pages
DL3797BPRI Installation Guide   Krystal Touch of NY DL3797BPRI Installation Guide, 1 pages
DL3797BPAS Installation Guide   Krystal Touch of NY DL3797BPAS Installation Guide, 1 pages
DL3800ABPRI Installation Guide   Krystal Touch of NY DL3800ABPRI Installation Guide, 1 pages
DL3606ABPRI Installation Guide   Krystal Touch of NY DL3606ABPRI Installation Guide, 1 pages
DL3615BPRI Installation Guide   Krystal Touch of NY DL3615BPRI Installation Guide, 1 pages
DL3733BPRI Installation Guide   Krystal Touch of NY DL3733BPRI Installation Guide, 1 pages
DL3733CPAS Installation Guide   Krystal Touch of NY DL3733CPAS Installation Guide, 1 pages
DL3801CPRI Installation Guide   Krystal Touch of NY DL3801CPRI Installation Guide, 1 pages
DL3611BPRI Installation Guide   Krystal Touch of NY DL3611BPRI Installation Guide, 1 pages
DL3615BPAS Installation Guide   Krystal Touch of NY DL3615BPAS Installation Guide, 1 pages