Source: DIN EN 15232
The table illustrates the relationship between
building automation functions and energy
effi ciency classes for control of the heating
system.
Defi nition of classes
Automatic control and regulation
of the heating system
Residential
building
Non-residential
building
DCB
A DCBA
Control of transfer
The controller is installed at transfer level or room level; in the former case, one controller can regulate a number of different rooms.
0 No automatic control xx
1 Central automatic regulation
xx x
2 Automatic individual room control using thermostatic valves or electronic control devices
xx xx
3 Individual room control with communication between control devices and BACs
xxx xxx
4 Integrated individual room control including needs-based regulation (occupancy, air quality, etc.)
xxx
x xxxx
Regulation of hot water temperature in distribution network (fl ow or return)
Comparable functions can be used to control networks for direct electrical heating.
0 No automatic control xx
1 Weather-based control
xx xx
2 Control of inside temperature
xxx
x xxxx
Control of circulation pumps
The controlled pumps can be installed in the network at different levels.
0 No control xx
1 On/off control
xx x
2 Control of variable pump speed according to a constant Δ p
xxx
x xxxx
3 Control of variable pump speed according to proportional Δ p
xxx
x xxxx
Control of transfer and/or distribution during intermittent operation
One controller can regulate different rooms/zones with the same occupancy pattern.
0 No automatic control xx
1 Automatic control with fi xed time program
xx x
2 Automatic control with optimised on/off switching
xxx
x xxxx
Control of generators
0 Constant temperature xx
1 Variable temperature dependent on the outside temperature
xxx
x xxxx
2 Variable temperature dependent on the load
xxx
x xxxx
Operating sequence of different generators
0 Priority setting based solely on the load x x x x
1 Priority setting based on the load and on the generator performance
xxx xxx
2 Priority setting based on the level of generator usage (check other norms)
xxx
x xxxx
We reserve the right to make technical changes.